        Advanced Control (EEEE4116)
        Coursework 1
        Modelling and Advanced Controller Design for a 2-Level Grid-Feeding Inverter
        In this assignment you will bring together your skills of state-space equation development and controller 
        design to control a grid-tied 2-Level Converter. The design will make use of transforming the 3-phase 
        behaviour of this converter into the dq frame and use the dq equivalent circuit to develop controls. If you 
        have not yet read the coursework summary, it is highly recommended you read this prior to get the 
        understanding of what dq transforms are and why we are developing a control system in this way. 
        Figure ** Notional System Diagram: DC Source interfaced with 3-phase 2-Level Inverter interfaced to the grid.
        The system under investigation is a very common application when trying to link renewable energy sources 
        such as solar panels, or energy storage systems to interface them to the national grid, or even microgrid 
        applications where small remote communities rely on generating their own power. 
        We are converting DC power into 3-phase AC power to connect to the national grid. The parameters which 
        will be used in the design is as follows: 
        Vdc DC Supply Voltage = 400V
        Vgrid Grid RMS Voltage = 230Vrms
        L Output Filter Inductance = **0mH
        R Intrinsic Filter Resistance = 2Ω
        C Output Filter Capacitance = 33uF
        ω Grid Frequency (rads-1
        ) = 100π rads-1
        fs
        Switching Frequency = 20kHz
        Exercise 1 – System Modelling 
        As per the coursework summary, we wish to develop our control strategy using the dq equivalent model. It 
        can be shown in [ X ] that an equivalent 3-phase inverter can be modelled using the following circuits when 
        observing converter dynamics in the dq domain:
        Figure 2- 3-Phase Inverter dq equivalent average model.
        Where: 
        • md: d-axis modulation index. 
        • mq: q-axis modulation index. 
        • ω: frequency of phase voltages (rads-1

        • Vcd / Vcq: d-axis and q-axis voltage respectively across capacitor
        • Iid / Iiq: d-axis and q-axis input current respectively from inverter
        • Icd / Icq: d-axis current respectively flowing into capacitor.
        • Iad / Iaq: d-axis and q-axis output currents after filter. 
        • represents a virtual voltage source in the system (due to changing currents in inductor)
        • represents a virtual current source in the system (due to changing voltages in capacitor)
        Hint: Note the directions of the virtual voltage and current sources. Vital to this exercise.
        Using Kirchhoff’s current and voltage laws on the two circuits shown in Figure 2, develop state-equations for d and q 
        axis voltage and currents. 
        In our system, we will treat the modulation indexes as inputs to our system. Using your state equations, go on to 
        show that the state-space equation defining the model can be shown to be as: 
        As you may have recognised, although Iad and Iaq are variables in our dq model, this variable is not included within 
        the state-equation. Similar could be said about Icd, and Icq. Explain why these terms are not present in the final 
        state-space equation. 
        In addition, what sources of error do you think could be attributed in the model, and what effect do you think this 
        could have on the system?
        Exercise 2 – Transfer Function Depiction 
        Whilst state-space can describe the system with differential equations, it still does not fully replace the 
        transfer function for model development. In fact, often a transfer function block diagram is first developed 
        to visualize the behaviours of a system and help formulate state-space models. 
        In the first part of this exercise, analyse Fig 2 and construct a transfer block diagram for the above model. A 
        template has been provided below to assist you construct the block diagram. Explain in your report how 
        you derived the terms in the block diagram.
        _
        _
        Figure 3: Structure of the block diagram for the dq equivalent model. Fill in the blanks and '?' to complete the model.
        The boxes with ‘?’ should be transfer functions in Laplace Form. The dashed boxes are interconnections 
        between terms to form the mathematical model of the system. 
        After constructing the model, in MATLAB enter your state-space system using the ss(A,B,C,D) command. 
        Compare the eigenvalues of the state-space representation to that of the transfer functions in Fig 3, and 
        can you explain why there is a discrepancy between them?
        As shown through the state-space equations, and the transfer function block diagram, the two circuits 
        exhibit cross-coupling (sharing of terms in each other’s models). Why is cross coupling an issue in the 
        controller design, and how could you augment the transfer block diagram to compensate for cross-coupling 
        affects?
        Exercise 3 – Control Philosophy 
        We have now derived the state-space equations for our inverter, and modelled the transfer function block 
        diagram, all within the dq domain. We will now start designing the controller for our inverter. 
        We want our converter to be able to respond quickly to any changes in demand from the grid. Therefore, a 
        settling time to maintain the peak voltage will be set to 200ms. This in turn will influence the phase change 
        of the inverter similarly. 
        Decide with explanation the choice of poles being used in the pole-placement algorithm and create 
        feedback controller K for our system. You can augment the system by feeding the output of the controller 
        directly into the B Matrix as follows:
        Figure 4: Basic state-space block diagram to analyse performance of designed controller.
        In default condition, you may see the output not change at all. What can you change in the above model to 
        evaluate the closed loop performance of the system.
        One you can see the dynamics of the outputs, evaluate the response, and reflect if the system is behaving 
        according to your design.
        You will realise from the system should operate much better than that of open loop, however there is 
        currently no ability to attain our desired voltages in this control scheme as we have no references for which 
        the controller can actuate upon. If you analyse the output of your controller ‘K’ when using the block 
        diagram in Fig 4, what are the outputs of K tending to, and can you explain why the system is tending to 
        this value. 
        To integrate references into our model, we must introduce integral states. Identify which states you'll 
        reference for grid applications. Discuss in your report how these integral states are added to the state space block diagram, and how they help achieve zero steady state error. Given the expanded state system, 
        reperform the pole-placement with new poles, justifying your selection while ensuring desired converter 
        performance.
        In the report, discuss the adaptation to the state-space equation to incorporate integral states, the need for 
        them, the design of the new poles for the system. Show, with explanations how the state-space block 
        diagram is augmented for the inclusion of integral states. Analyse the performance of the system, especially 
        any foreseeable issues you can observe with the system? Prove to the reader that even with the 
        adaptation, the system operates still within desired specification. 
        Exercise 4 – Integrator Preloading and Integrator Anti windup Implementations
        Integrator terms are very influential regarding system performance. It’s not simply that having them in our 
        system allows our system to achieve zero steady state error but can also heavily influence the start-up 
        performance of any control system, and the step response of a system when there are physics limitations.
        Using the working closed loop model with integral states, place a scope on each of the integrator outputs
        (that for the states as well as integral states) and the system outputs. 
        Figure 5: Placement of Scope on Output of integrator block
        What do you observe in the relationship between the integrator outputs and the system outputs?
        A solution to the issues observed is to do something called Integrator Pre-Loading. You may have in the past 
        used the PI block within Simulink and seen the following option to initialize the integrator values but may 
        not have realised the use in this up until this exercise. 
        Figure 6: Initialization Settings within the PI Block in Simulink
        You should hopefully recognise that these integrator values reach a steady value when all the system 
        derivatives equate to zero. Note these values down, and inside your integrator block, initialise the 
        integrator to these values. 
        In doing this, what has changed in the system? Can you explain with reference to the state-space system 
        why the system now behaves the way it does? What assumptions are made performing this change, and 
        can would anything need to be considered when apply on physical hardware?
        Your system should be working incredibly well, in comparison to Exercise 3. However, there is still one issue 
        that still needs to be resolved regarding the integrator. You probably will not see the issue if you have 
        incorporated the integrator pre-loading successfully, so we need to do a step test to highlight this issue. 
        The following would typically be quite irregular for a grid tied inverter, but we are doing this to push the 
        system into new behaviour. Use a ‘Step’ block on one of your references and apply a sizeable step input at 
        half your simulation time (enough time to allow the system to stabilize before the step reference is 
        applied). What can you observe happen with the system inputs, and why is this an issue? (If you don’t see 
        any issues, apply larger steps, and analyse all states and inputs until a possible issue may arise)
        We need to limit the effects of this issue, which raises the issue if integrator anti-windup. If a controller has 
        an integrator, integrator anti-windup means that the integrator is turned off, when the when the system 
        hits limit values (or “Saturates”). Can you explain why we would want to turn off the integrator when our 
        system reaches these conditions?
        In Figure 7 is the typical structure of an integrator anti-windup. Analyse the structure, adapt your system to 
        incorporate the Anti-windup scheme below. Clearly describe your methodology and show you understand 
        what is going on when you incorporate into your system.
        Figure 7: Integrator Anti-windup Structure
        If in your system for example, you want to limit u to ±60, the look-up table can be as follows:
        Input -100 -60 -59.9 0 59.9 60 100
        Output 0 0 1 1 1 0 0
        Exercise 5 – Real Model Testing
        The final part to this coursework is to apply our controller model to an actual circuit to show what has been 
        designed would work. Here it is not expected that you build up a whole inverter simulation, and you will be 
        provided with the backbone of the inverter model as shown in Fig 8.
        To the simulation, you may choose two pieces of software, MATLAB Simulink, or PLECS. Please ensure you 
        download the respective file for the application you wish to use. PLECS simulates power systems faster, but 
        MATLAB is easier to implement the observer design through script. Both pieces of software will produce 
        the same results for the same system.
        Figure 8: Simulink Model of Three-Phase Inverter which can be downloaded on Moodle.
        You task here is to adapt the model to incorporate the controller, into the switching model. One 
        implemented, stress test your controller, note any differences between the average model you made for 
        Exercises **4, and try and explain why such differences are observed. You may notice that Iiq is a non-zero 
        value when the system reaches steady state. Can you explain why Iiq is the value to which it settles at?
        Stress testing can involve load testing using the connected resistors and apply the switch at a given 
        moment in time. Can change the reference values.
        What happens to the system is you set the resistors to be a very low value (approx. 100Ω)? Can you explain 
        why the converter behaves in this way?
        Exercise 6 – Optimal Controllers Development
        The methods of controller design covered in this coursework has been a very popular industrial method of 
        controller design for many years, and you have in fact used similar techniques when designing PI controllers 
        in your previous studies. However, as computers have become faster, and algorithms refined, techniques of 
        controller optimisation have been rapidly employed in industrial applications. 
        In this exercise, we will briefly look at the Linear Quadratic Regulator (LQR). The mathematics of the control 
        is relatively complex and out of the scope for this module, however it is important to understand how you 
        can use software tools such as MATLAB to develop optimal controllers for state-space systems. 
        What is LQR Control? 
        The Linear Quadratic Regulator is an Optimal Control method, which looks at how to drive a system from its
        current states to the required reference states at a minimal cost, or in other words, to achieve our system 
        references using the least amount of energy. 
        To achieve this, the following cost function is evaluated:
        min 𝐽 (w**6;) = ∫(w**9;
        𝑇𝑄w**9; + w**6;
        𝑇𝑅w**6;)

        0
        Where the feedback control law, as normal is defined by Eq. 3:
        w**6; = −𝐾w**9;
        Therefore, the algorithm looks for a value for a controller K, which not only makes the closed loop system 
        stable, but minimizes the overall control effort J.
        The way we can tune this system is by selection of the Q and R matrices. With reference to Eq. 2 you can 
        see that the Q matrix weights the states ‘x’, and the R matrix weights the inputs ‘u’.
        The Q and R matrices are each diagonal matrices, whose dimensions are equivalent to the number of 
        states, and inputs respectively. For example, for our system we would have the following matrices, if Q and 
        R are set to unity. 
        𝑄
        6×6 = [
        1

        1
        ],𝑅
        2×2 = [
        1
        0
        0
        1
        ]
        Each diagonal element in the Q matrix corresponds to the state of that row. For example, the non-zero 
        value on the 2nd row of Q, associates a weighting to the 2nd states of x, in this case Iiq.
        Likewise, for R, the non-zero value on the 1st row of R corresponds to the 1st input, in this case md.
        Tuning the controller can be done by understanding these rules:
        • Q Matrix Tuning
        o The smaller the weighting in given states, the more controller effort provided to this state. In 
        other words, the smaller the value, the faster the bandwidth for that given state.
        • R Matrix Tuning
        o The larger the weighting given to the inputs, the more restricted the respective input.
        ▪ So, a smaller value for R, the faster an input can react to system changes.
        ▪ A larger value for R, the more restricted, and thus slower an input would react. 
        Eq. 2
        Eq. 3
        Eq. 4
        For this exercise, you are going to develop an LQR controller, making use of the lqr() function within 
        MATLAB. The control architecture will not need any change to that from Exercise 4 & 5. 
        Read through the documentation of the lqr() function in MATLAB and ensure you know how to use the 
        function. 
        In your report, describe the process of designing the LQR controller, noting that we still desire our system to 
        stabilise at our references within 200ms. Show a good design philosophy and describe the process in which 
        you designed the controller to meet the specification. You may also want to think about the following 
        questions in your report when writing about your design:
        What performance improvement can you observe between the controller designed using LQR and pole placement in our closed loop system?
        What are the fundamental differences between LQR and other control techniques such as pole-placement, 
        and what advantages can use LQR optimisation, and which scenarios might it be a preferable method of 
        design? 
        What are the trade-offs involved when choosing the weightings in Q and R? Can you show the impact of 
        changing each of the matrices and relate it back to theory?
        Given the name of this controller is a Linear Quadratic Regulator, do you believe these controllers would 
        work well in non-linear environment, and if not, are there some work arounds you could propose?
        Writing your report
        The style of the report should be a technical report. You may use the headings for each exercise to break 
        down the subheadings in your report, but the style of the report you submit for your assignment should be 
        in the style as if you were creating a professional document colleagues may look to understand your design.
        Do not write your report as if answering an exam, i.e Ex5 a) Ex5 b). Doing this you will lose marks in 
        presentation for your report.
        Each exercise has a few questions which you are expected to answer, however if there are other elements 
        of the design which you wish to discuss and analyse further based on your studies on the course or extra 
        reading, you are highly encouraged to write up on this. This is how you will achieve the top marks in the 
        rubric. 
        Coursework Support Sessions
        Each week there is a coursework support session on teams. This is your opportunity to ask any questions 
        relating to the coursework, from use of MATLAB, Simulink, or general theory on controller design. You’re 
        highly encouraged to attend each of the seminars each week and come prepared with questions.
        The support sessions take the following structure each week:
        • First 10-15 minutes will involve a small presentation or demonstration on different aspects of the 
        controller design, or small software tutorial.
        • Remaining 45 minutes will be a group Q&A. Please do have questions ready as this part of the 
        session is directed by you. 
        • If there is time remaining **to-1 help sessions can take place. It will be first come first serve. If I am 
        unable to get to people requested, I will attempt to meet you another time in the week when I am 
        free. 
        For any coursework questions, please contact Dr. David Dewar (David.Dewar1@nottingham.ac.uk). 
        Submission Requirements:
        This report should be no longer than 20 pages (title pages and contents page are not included) 
        Please do not include anything which might identify you as the writer of the report. All reports are to be 
        marked anonymously. 
        Therefore, please DO NOT INCLUDE any names, student ID’s or emails in the document. 

        請(qǐng)加QQ:99515681  郵箱:99515681@qq.com   WX:codinghelp







         

        掃一掃在手機(jī)打開當(dāng)前頁(yè)
      1. 上一篇:COMP0035代做、代寫python程序語(yǔ)言
      2. 下一篇:代寫CPTG1405、代做Python設(shè)計(jì)程序
      3. 無(wú)相關(guān)信息
        合肥生活資訊

        合肥圖文信息
        挖掘機(jī)濾芯提升發(fā)動(dòng)機(jī)性能
        挖掘機(jī)濾芯提升發(fā)動(dòng)機(jī)性能
        戴納斯帝壁掛爐全國(guó)售后服務(wù)電話24小時(shí)官網(wǎng)400(全國(guó)服務(wù)熱線)
        戴納斯帝壁掛爐全國(guó)售后服務(wù)電話24小時(shí)官網(wǎng)
        菲斯曼壁掛爐全國(guó)統(tǒng)一400售后維修服務(wù)電話24小時(shí)服務(wù)熱線
        菲斯曼壁掛爐全國(guó)統(tǒng)一400售后維修服務(wù)電話2
        美的熱水器售后服務(wù)技術(shù)咨詢電話全國(guó)24小時(shí)客服熱線
        美的熱水器售后服務(wù)技術(shù)咨詢電話全國(guó)24小時(shí)
        海信羅馬假日洗衣機(jī)亮相AWE  復(fù)古美學(xué)與現(xiàn)代科技完美結(jié)合
        海信羅馬假日洗衣機(jī)亮相AWE 復(fù)古美學(xué)與現(xiàn)代
        合肥機(jī)場(chǎng)巴士4號(hào)線
        合肥機(jī)場(chǎng)巴士4號(hào)線
        合肥機(jī)場(chǎng)巴士3號(hào)線
        合肥機(jī)場(chǎng)巴士3號(hào)線
        合肥機(jī)場(chǎng)巴士2號(hào)線
        合肥機(jī)場(chǎng)巴士2號(hào)線
      4. 幣安app官網(wǎng)下載 短信驗(yàn)證碼 丁香花影院

        關(guān)于我們 | 打賞支持 | 廣告服務(wù) | 聯(lián)系我們 | 網(wǎng)站地圖 | 免責(zé)聲明 | 幫助中心 | 友情鏈接 |

        Copyright © 2024 hfw.cc Inc. All Rights Reserved. 合肥網(wǎng) 版權(quán)所有
        ICP備06013414號(hào)-3 公安備 42010502001045

        主站蜘蛛池模板: 欧美成人aaa片一区国产精品 | 韩国理伦片一区二区三区在线播放 | 亚洲一区二区三区乱码A| 在线观看中文字幕一区| 91精品一区二区| 国产丝袜视频一区二区三区| 一区二区在线视频免费观看| 一区二区在线视频| 亚洲国产精品一区| 久久精品无码一区二区三区| 人妻体内射精一区二区| 女人和拘做受全程看视频日本综合a一区二区视频| 精品国产一区二区三区免费| 国产乱码精品一区二区三| 精品在线视频一区| 男人的天堂精品国产一区| 视频一区二区在线播放| 波多野结衣电影区一区二区三区| 成人精品一区二区激情| 日本高清天码一区在线播放| 无码中文人妻在线一区 | 午夜福利国产一区二区| 国产一区高清视频| 一区二区三区午夜| 中文字幕一区二区三区在线播放| aⅴ一区二区三区无卡无码| 福利一区国产原创多挂探花| 亚洲国模精品一区| 国产av天堂一区二区三区| 精品一区二区三区中文字幕| 亚洲国产精品一区第二页| 日本午夜精品一区二区三区电影| 亚洲视频免费一区| 久久精品成人一区二区三区| 精品国产免费观看一区| 精品视频一区二区观看| 国产成人精品一区二区三区无码| 一本大道东京热无码一区| 亚洲区精品久久一区二区三区| 日韩一区二区在线播放| 国产在线精品一区在线观看|